HomeMy WebLinkAboutPermit File BLD-2023-0024 4405 E Avenue (3)DEBORAH ANNE AYRS RESPONSE LETTER Listed below are the revisions we have made to the design and engineering letter document for our Residential Solar Installation for Deborah Anne Ayrs. Design Page 1:COVER PAGE ●Updated photo-voltaic (PV)system specs and Site Information,With AC system size from 3.60 kW AC &4.80 kW DC to 3.00 kW AC &4.50 kW DC.Changing the corresponding Module and inverters needed to install. ●Updated PV Modules from (12)Hanwha Q.Peak Duo L-G7.3 (400W)to (10)VSUN-144BMH-DG (450W) ●Updated (3)Hoymiles HM-1200N to (2)Hoymiles HM-1200N and add 1 Hoymiles HM-600N Inverters Design Page 2:SITE PLAN ●Updated Panels based on the number of counts of Contract Documents from 12 Panels to 10 Panels. ●Updated the panel arrangement. Design Page 3:ROOF ATTACHMENT &MOUNTING DETAIL ●Modified and indicates appropriate PV Modules being used with corresponding hatch and numbering. ●Updated Photo-voltaic Array Structural Criteria from Hanwha Q.Peak Duo L-G7.3(400W)to VSUN-144BMH-DG (450W) ●Updated the panel arrangement and the equipment Information. Design Page 4:RACKING &MOUNTING DETAIL ●Updated Photo-voltaic Array Structural Criteria from Hanwha Q.Peak Duo L-G7.3 (400W)to VSUN-144BMH-DG (450W) ●Updated Equipment Information. Design Page 5:LINE DIAGRAM ●Updated the Inverter Specs and Schedule of Equipment and Conduit size of Tag#2 under the Conduit and Conductor Schedule from 3/4"PVC to 3/4 EMT. ●Updated the diagram showing changes in the equipment being used in the design from (12 Modules to 10 Modules) ●Updated (3)Hoymiles HM-1200N to (2)Hoymiles HM-1200N and add (1)Hoymiles HM-600N Design Page 6:ELECTRICAL CALCS ●Updated the Inverter Specs and Schedule of Equipment and Conduit size of Tag#2 under the Conduit and Conductor Schedule from 3/4"PVC to 3/4 EMT. ●Updated Inverter Model(s)from (3)Hoymiles HM-1200N to (2)Hoymiles HM-1200N and add (1)Hoymiles HM-600N ●Updated Max AC Current from 18.8A to 15.63 ●Updated Max AC Output Power from 3600W to 3000W ●Updated Total Max AC Current from 15.00A to 12.5A Design Page 7:LABELS ●Updated the AC disconnect rated output and label codes to NEC 2020 ●Updated the Rated AC Output Current from 15 A to 12.5 A Design Page 8:PLACARD ●Updated Panels based on the number of counts of Contract Documents from 12 Panels to 10 Panels. ●Updated PV Modules from Hanwha Q.Peak Duo L-G7.3 (400W)to VSUN-144BMH-DG (450W) Spec Sheets:Provide Spec sheets of PV Modules from Hanwha Q.Peak Duo L-G7.3 (400W)to VSUN-144BMH-DG (450W)and Hoymiles HM-1200N and add Hoymiles HM-600N inverters CITY OF ANACORTES PLANNING AND BUILDING DEPT: APPROVED PLANS REVIEWED FOR CODE COMPLIANCE PERMIT #:______________________________ ADDRESS:____ _______________ APPROVED BY: ______________ SUBJECT TO FIELD INSPECTION. APPROVED PLANS SHALL NOT BE ALTERED WITHOUT AUTHORIZATION. BLD-2023-0024 4405 E Ave AERIAL VIEW:MAP VIEW: GENERAL NOTES 1. INSTALLATION OF SOLAR PHOTOVOLTAIC SYSTEM SHALL BE IN ACCORDANCE WITH NEC ARTICLE 690, AND ALL OTHER APPLICABLE NEC CODES WHERE NOTED OR EXISTING 2. PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSED ELECTRICAL EQUIPMENT WILL COMPLY WITH NEC ARTICLE 110 3. ALL WIRES, INCLUDING THE GROUNDING ELECTRODE CONDUCTOR SHALL BE PROTECTED FROM PHYSICAL DAMAGE IN ACCORDANCE WITH NEC ARTICLE 250 4. THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE; THIS SYSTEM IS UTILITY INTERACTIVE PER UL 1741 AND DOES NOT INCLUDE STORAGE BATTERIES OR OTHER ALTERNATIVE STORAGE SOURCES 5. ALL DC WIRES SHALL BE SIZED ACCORDING TO [NEC 690.8] 6. DC CONDUCTORS SHALL BE WITHIN PROTECTED RACEWAYS IN ACCORDANCE WITH [NEC 690.31] 7. ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL JURISDICTIONAL BUILDING CODE PHOTOVOLTAIC (PV) SYSTEM SPECIFICATIONS APPLICABLE GOVERNING CODES SITE SPECIFICATIONS OCCUPANCY: R-3 ZONING: RESIDENTIAL COVER PAGE - PV01 SITE INFORMATION DEBORAH ANNE AYRS 4405 E AVE ANACORTES, WA 98221 DC System Size: 4.50 kW DC Lat, 48.48544 Long, -122.63078 (10) VSUN450 -144BMH-DG (450W) PV Modules Inverter(s) PUGET SOUND ENERGY DRAWN BY: B CUTANDA DATE: 05/15/2023 9981 West 190th St Unit K Mokena IL 60448 T: 708-995-1643 Revolution Energy Systems Inc. (2)HOYMILES HM-1200N (240V) (1) HOYMILES HM-600N (240V) AC System Size: 3.00 kW AC / 3.00 kVA 2020 NEC 2018 IRC 2018 IMC 2018 IFGC EQUIPMENT: AC System Size: 3.00 kW AC / 3.00 kVA DC SYSTEM SIZE: 4.50 kW DC (10)VSUN450 -144BMH-DG (450W) PV Modules (2)HOYMILES HM-1200N (240V) INVERTERS (1) HOYMILES HM-600N (240V) INVERTERS RACKING: S-5 MINI/S BRACKET - 48" O.C. SHEET INDEX: PV01 COVER PAGE PV02 SITE PLAN PV03 ROOF ATTACHMENTS PV04 MOUNTING DETAIL PV05 LINE DIAGRAM PV06 ELECTRICAL CALCS PV07 LABELS PV08 PLACARD PV09 SITE PHOTOS AC M MSP LC JB AC M MSP LC JB SITE INFORMATION DEBORAH ANNE AYRS 4405 E AVE ANACORTES, WA 98221 DC System Size: 4.50 kW DC Lat, 48.48544 Long, -122.63078 (10) VSUN450 -144BMH-DG (450W) PV Modules Inverter(s) PUGET SOUND ENERGY DRAWN BY: B CUTANDA DATE: 05/15/2023 9981 West 190th St Unit K Mokena IL 60448 T: 708-995-1643 Revolution Energy Systems Inc. (2)HOYMILES HM-1200N (240V) (1) HOYMILES HM-600N (240V) AC System Size: 3.00 kW AC / 3.00 kVA SITE PLAN - PV02 MOUNTING PLANE: MP1 ARRAY DETAILS: AZIMUTH: 270° TILT: 28° VISIBLE, LOCKABLE, LABELED AC DISCONNECT LOCATED WITHIN 10' OF UTILITY METER CLOSE UP OF HOUSE MSP M UTILITY METER PV AC VISIBLE, LOCKABLE, LABELED AC DISCONNECT METER SOCKET (For utility PV meter) INV C INVERTER EQUIPMENT LEGEND: SUB PANEL COMBINER BOX LC BATT SD JB PV MODULES PROPERTY LINE SUB LOAD CENTER BATTERY(IES)JUNCTION BOXMAIN SERVICE PANEL SERVICE DISCONNECT SS SMART SWITCH (IQ System Controller) FIRE ACCESS PATHWAY (3' TYP) ATS AUTOMATIC TRANSFER SWITCH OR C H A R D A V E PROPERTY LINE ~179'-9'' PROPERTY LINE ~179'-9'' PR O P E R T Y L I N E ~ 1 7 3 ' - 6 ' ' PR O P E R T Y L I N E ~ 1 7 3 ' - 6 ' ' MP 1 DRIVEWAY (E) SKY LIGHT 36'-5" 45'-6" 78'-1" 68'-3" AC M MSP LC JB SITE INFORMATION DEBORAH ANNE AYRS 4405 E AVE ANACORTES, WA 98221 DC System Size: 4.50 kW DC Lat, 48.48544 Long, -122.63078 (10) VSUN450 -144BMH-DG (450W) PV Modules Inverter(s) PUGET SOUND ENERGY DRAWN BY: B CUTANDA DATE: 05/15/2023 9981 West 190th St Unit K Mokena IL 60448 T: 708-995-1643 Revolution Energy Systems Inc. (2)HOYMILES HM-1200N (240V) (1) HOYMILES HM-600N (240V) AC System Size: 3.00 kW AC / 3.00 kVA ROOF ATTACHMENTS - PV03 PV MODULE COUNT: ARRAY AREA: ROOF AREA: PHOTOVOLTAIC ARRAY STRUCTURAL CRITERIA: 10 PERCENT OF ROOF COVERED: ARRAY WEIGHT: POINT LOAD: DISTRIBUTED LOAD: (lbs/ft²) 2585.8006 ft² 9% MODULE COUNT * 61.29 lbs = 612.90 lbs MODULE COUNT * 23.94 ft² = 239.40 ARRAY LBS/ATTACHMENTS = 18.03 (ARRAY) WEIGHT/AREA = 2.6 lbs/ft² HOUSE ELEVATION EQUIPMENT INFORMATION: RAIL MANUFACTURER: RAIL PART NUMBER: ATTACHMENTS ATTACHMENT QTY: SPLICE QTY: MIDCLAMP QTY: ENDCLAMP QTY: UNIRAC SM S-5 MINI/S BRACKET 34 7 24 9 ROOF TYPE: ROOF FRAMING: RAFTER/TOP CHORD SIZE: RAFTER/TOP CHORD SPACING: ATTACHMENT SPACING: ROOF INFORMATION METAL ROOF MANUFACTURED TRUSS 2" X 4" 24" 48" ±17'-10" 30' 46'-10"58'-10" 30' 3" TYP 3' TYP 1-1 = HM1200N =HM600N HOYMILES INVERTER LEGEND: 1-1 1-1 1-1 1-2 1-2 1-2 1-2 1-3 1-3 SITE INFORMATION DEBORAH ANNE AYRS 4405 E AVE ANACORTES, WA 98221 DC System Size: 4.50 kW DC Lat, 48.48544 Long, -122.63078 (10) VSUN450 -144BMH-DG (450W) PV Modules Inverter(s) PUGET SOUND ENERGY DRAWN BY: B CUTANDA DATE: 05/15/2023 9981 West 190th St Unit K Mokena IL 60448 T: 708-995-1643 Revolution Energy Systems Inc. (2)HOYMILES HM-1200N (240V) (1) HOYMILES HM-600N (240V) AC System Size: 3.00 kW AC / 3.00 kVA UNIRAC PRO SERIES END CLAMP UNIRAC PRO SERIES MID CLAMP 1 2 PV MODULE RAIL PV MODULE RAIL PV MODULE 1'-8" MAX. RAIL FRONT VIEW 1 END CLAMP DETAILS 2 MID CLAMP DETAILS RAIL S-5 MINI/S BRACKET 10" MIN - 1'-4" MAX 2'-8" MIN - 3'-10" MAX (E) RAFTER/TOP CHORD 2'-8" MIN - 3'-10" MAX 3 10" MIN - 1'-4" MAX (E) RAFTER/TOP CHORDS 48" MAX SPAN SIDE VIEW 3 DETAIL, MOUNTING MOUNTING DETAIL - PV04 PV MODULE COUNT: ARRAY AREA: ROOF AREA: PHOTOVOLTAIC ARRAY STRUCTURAL CRITERIA: 10 PERCENT OF ROOF COVERED: ARRAY WEIGHT: POINT LOAD: DISTRIBUTED LOAD: (lbs/ft²) 2585.8006 ft² 9% MODULE COUNT * 61.29 lbs = 612.90 lbs MODULE COUNT * 23.94 ft² = 239.40 ARRAY LBS/ATTACHMENTS = 18.03 (ARRAY) WEIGHT/AREA = 2.6 lbs/ft² EQUIPMENT INFORMATION: RAIL MANUFACTURER: RAIL PART NUMBER: ATTACHMENTS ATTACHMENT QTY: SPLICE QTY: MIDCLAMP QTY: ENDCLAMP QTY: UNIRAC SM S-5 MINI/S BRACKET 34 7 24 9 ROOF TYPE: ROOF FRAMING: RAFTER/TOP CHORD SIZE: RAFTER/TOP CHORD SPACING: ATTACHMENT SPACING: ROOF INFORMATION METAL ROOF MANUFACTURED TRUSS 2" X 4" 24" 48" SITE INFORMATION DEBORAH ANNE AYRS 4405 E AVE ANACORTES, WA 98221 DC System Size: 4.50 kW DC Lat, 48.48544 Long, -122.63078 (10) VSUN450 -144BMH-DG (450W) PV Modules Inverter(s) PUGET SOUND ENERGY DRAWN BY: B CUTANDA DATE: 05/15/2023 9981 West 190th St Unit K Mokena IL 60448 T: 708-995-1643 Revolution Energy Systems Inc. (2)HOYMILES HM-1200N (240V) (1) HOYMILES HM-600N (240V) AC System Size: 3.00 kW AC / 3.00 kVA LINE DIAGRAM - PV05 TYPE: MODULES: INVERTER: AC DISCONNECT: QTY: (10) (1) DESCRIPTION: VSUN450 -144BMH-DG 450 PV AC Disconnect, 240V, 2-Pole w/ 20A fuses RATING: 450 W 60 A Equipment Schedule 4 1 (2) (1)THWN-2 COPPER - (GROUND)N/A - FREE AIR 2 (2) (1)10 AWG (90°C) THHN/THWN-2, COPPER - (L1, L2) THWN-2 COPPER - (GROUND)3/4" EMT TAG QTY WIRE GAUGE Conduit & Conductor Schedule DESCRIPTION CONDUIT SIZE VSUN450 -144BMH-DG 450 Specs POWER MAX (PMAX): OPEN CIRCUIT VOLTAGE (VOC): MAX POWER-POINT CURRENT (IMP): MAX POWER-POINT VOLTAGE (VMP): SHORT CIRCUIT CURRENT (ISC): SERIES FUSE RATING: 450W 20A 494V 10.93A 41.2V 11.52A LINE SIDE TAP USING INSULATION PEIRCING 705.11(A) (E) G (E) UTILITY METER (E) GROUNDING ELECTRODE N (E) LOADS (E) 200A MAIN SERVICE PANEL (E) 200A-2P 120/240 VAC TO UTILITY GRID (E) LOADS CONNECTION AS A LINE/SUPPLY SIDE CONNECTION - NEC 705.11(A) HOYMILES HM-600N (240V)600 W(1) AC-CABLE , COPPER (L1, L2) 3 LOAD CENTER:(1)PV LOAD CENTER, NEMA 3R RATED GND 2P - 20A J-BOX 1 2 STRING (1): 20.0 A DC (10 MODULES) 4 MODULES === 690.12 RAPID SHUTDOWN COMPLIANT (N) 240V/125A PV LOAD CENTER, NEMA 3R RATED VISIBLE, LOCKABLE, LABELED AC DISCONNECT LOCATED WITHIN 10' OF UTILITY METER 125 A 10 AWG (90°C) 12 AWG (90°C) 12 AWG (90°C) 10 AWG (90°C) 10 AWG (90°C) THHN/THWN-2, COPPER - (L1, L2, NEUTRAL) THWN-2 COPPER - (GROUND)3/4" PVC3(1) (2) THHN/THWN-2, COPPER - (L1, L2, NEUTRAL) THWN-2 COPPER - (GROUND)4 (3) (1) 6 AWG (75°C) 6 AWG (75°C)3/4" PVC HM-1200N 4 MODULESHM-1200N 2 MODULESHM-600N HOYMILES HM-1200N Specs MAX INPUT VOLTAGE: MAX INPUT CURRENT: NOMINAL DC INPUT VOLTAGE: MAXIMUM OUTPUT POWER: NOM. OUTPUT VOLTAGE: MAX OUTPUT CURRENT: 1-Phase, 60 HZ, UL 1741 Listed 60 V 20 A 60 V 1200 W 240 V 5.00 A PV AC DISCONNECT 60A VISIBLE, LOCKABLE, LABELED, OPEN 240V, 2-POLE WITH 20A FUSES N G HOYMILES HM-600N INVERTERS Specs MAX INPUT VOLTAGE: MAX INPUT CURRENT: NOMINAL DC INPUT VOLTAGE: MAXIMUM OUTPUT POWER: NOM. OUTPUT VOLTAGE: MAX OUTPUT CURRENT: 1-Phase, 60 HZ, UL 1741 Listed 60 V 20 A 60 V 600 W 240 V 2.50 A INVERTERS:HOYMILES HM-1200N (240V)1200 W(2) ELECTRICAL CALCS - PV06 SYSTEM OCPD CALCULATIONS INVERTER MODEL(S): # OF INVERTER(S): MAX OUTPUT CURRENT: (# OF INVERTERS) X (MAX OUTPUT CURRENT) X 125% <= OCPD RATING SITE INFORMATION DEBORAH ANNE AYRS 4405 E AVE ANACORTES, WA 98221 DC System Size: 4.50 kW DC Lat, 48.48544 Long, -122.63078 (10) VSUN450 -144BMH-DG (450W) PV Modules Inverter(s) PUGET SOUND ENERGY DRAWN BY: B CUTANDA DATE: 05/15/2023 9981 West 190th St Unit K Mokena IL 60448 T: 708-995-1643 Revolution Energy Systems Inc. (2)HOYMILES HM-1200N (240V) (1) HOYMILES HM-600N (240V) AC System Size: 3.00 kW AC / 3.00 kVA PV LOAD CALCULATIONS: SUPPLY SIDE TIE-IN FEEDER WIRE RATING: (FEEDER RATING ÷ 1.25) 200A 160.0000A (FEEDER WIRES ALLOWABLE SOLAR) 160.0000A (AVAILABLE FOR PV) ALLOWABLE SOLAR CALCULATION 2 5.00A HOYMILES HM-1200N (240V) (12.5 X 1.25) = 15.63A <= 20A, OK STRING CALCULATIONS HOYMILES : HM-1200N (240V), HM-600N (240V) MAX AC CURRENT MICRO INVERTER(S) IN SERIES: NOMINAL VOLTAGE / RANGE²: MAX AC OUTPUT POWER: ARRAY DC POWER: TOTAL MAX AC CURRENT: STRING #1 3 211V - 264V 3000W 4500W 12.5A TAG QTY DESCRIPTION CONDUIT SIZE CONDUCTOR RATING Conduit & Conductor Schedule CONDUCTOR TEMP. RATE AMBIENT TEMP # OF CONDUCTORS DERATE CONDUCTOR RATING W/DERATES CONDUIT FILLTEMP. DERATEWIRE GAUGE 10 AWG 10 AWG 3/4" EMT 40A 90°C 41.6A 11.45 %THHN/THWN-2, COPPER - (L1, L2) THWN-2 COPPER - (GROUND)(1) (2)22°C 1.0 1 (1) (2) 12 AWG 12 AWG THWN-2 COPPER - (GROUND)N/A - FREE AIR 30A 90°C 22°C N/A - FREE AIR 31.2A N/A - FREE AIR 2 AC-CABLE , COPPER (L1, L2) 15.63A NUMBER OF CURRENT CARRYING CONDUCTORS 4-6 7-9 10-20 PERCENT OF VALUES .80 .70 .50 GROUNDING & GENERAL NOTES: 1. PV INVERTER IS UNGROUNDED, TRANSFORMER-LESS TYPE. 2. DC GEC AND AC EGC TO BE SPLICED TO EXISTING ELECTRODE 3. ANY EXISTING WIRING INVOLVED WITH PV SYSTEM CONNECTION THAT IS FOUND TO BE INADEQUATE PER CODE SHALL BE CORRECTED PRIOR TO FINAL INSPECTION. 4. JUNCTION BOX QUANTITIES, AND PLACEMENT SUBJECT TO CHANGE IN THE FIELD - JUNCTION BOXES DEPICTED ON ELECTRICAL DIAGRAM REPRESENT WIRE TYPE TRANSITIONS. 5. AC DISCONNECT NOTED IN EQUIPMENT SCHEDULE OPTIONAL IF OTHER AC DISCONNECTING MEANS IS LOCATED WITHIN 10' OF SERVICE DISCONNECT. INTERCONNECTION NOTES: 1. INTERCONNECTION SIZING, LIMITATIONS AND COMPLIANCE DETERMINED IN ACCORDANCE WITH [NEC 705.12], AND [NEC 690.64]. 2. GROUND FAULT PROTECTION IN ACCORDANCE WITH [NEC 215.9], [NEC 230.95] AND [NEC 690.5] 3. ALL EQUIPMENT TO BE RATED FOR BACKFEEDING. 4. PV BREAKER TO BE POSITIONED AT THE OPPOSITE END OF THE BUSBAR RELATIVE TO THE MAIN BREAKER. DISCONNECT NOTES 1. DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH IS OPENED THE CONDUCTORS REMAINING LIVE ARE CONNECTED TO THE TERMINALS MARKED “LINE SIDE” (TYPICALLY THE UPPER TERMINALS) 2. AC DISCONNECT MUST BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL, BE LOCKABLE, AND BE A VISIBLE-BREAK SWITCH 90°C10 AWG 10 AWG 40A 12.03 %THHN/THWN-2, COPPER - (L1, L2, NEUTRAL) THWN-2 COPPER - (GROUND)3 (2) (1)22°C 1.043/4" PVC 75°CTHHN/THWN-2, COPPER - (L1, L2, NEUTRAL) THWN-2 COPPER - (GROUND)4 (3) (1)22°C 1.05 38.37 %6 AWG 6 AWG 65A 68.25A3/4" PVC 1.04 1.04 1.0 1.0 41.6A (# OF INVERTERS) X (MAX OUTPUT CURRENT) 1 2.50A HOYMILES HM-600N (240V) 10A 2.50A SITE INFORMATION DEBORAH ANNE AYRS 4405 E AVE ANACORTES, WA 98221 DC System Size: 4.50 kW DC Lat, 48.48544 Long, -122.63078 (10) VSUN450 -144BMH-DG (450W) PV Modules Inverter(s) PUGET SOUND ENERGY DRAWN BY: B CUTANDA DATE: 05/15/2023 9981 West 190th St Unit K Mokena IL 60448 T: 708-995-1643 Revolution Energy Systems Inc. (2)HOYMILES HM-1200N (240V) (1) HOYMILES HM-600N (240V) AC System Size: 3.00 kW AC / 3.00 kVA LABELS - PV07 RATED AC OUTPUT CURRENT: NOMINAL OPERATING AC VOLTAGE: PHOTOVOLTAIC AC DISCONNECT 240 V 7 LABELING NOTES: 1. LABELS CALLED OUT ACCORDING TO ALL COMMON CONFIGURATIONS. ELECTRICIAN TO DETERMINE EXACT REQUIREMENTS IN THE FIELD PER CURRENT NEC AND LOCAL CODES AND MAKE APPROPRIATE ADJUSTMENTS. 2. LABELING REQUIREMENTS BASED ON THE 2020 NATIONAL ELECTRIC CODE, OSHA STANDARD 19010.145, ANSI Z535. 3. MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION. 4. LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED [NEC 110.21(B)(3)] 5. LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8", WHITE ON RED BACKGROUND; REFLECTIVE, AND PERMANENTLY AFFIXED [IFC 605.11.1.1] 5 (ONLY IF PV INTERCONNECTION CONSISTS OF LOAD SIDE BREAKER) 3 5 (ONLY IF PV INTERCONNECTION CONSISTS OF LOAD SIDE BREAKER) 9 1 6 INTEGRATED DC DISCONNECT *ELECTRICAL DIAGRAM SHOWN ABOVE IS FOR LABELING PURPOSES ONLY. NOT AN ACTUAL REPRESENATION OF EQUIPMENT AND CONNECTIONS TO BE INSTALLED. LABEL LOCATIONS PRESENTED MAY VERY DEPENDING ON TYPE OF INTERCONNECTION METHOD AND LOCATION PRESENTED ON THE ELECTRICAL DIAGRAM PAGE. 6 4 LABEL 1 [NEC 690.13(B) AND NEC 690.15(C) ] LABEL 2 [NEC 705.12 (B) (3) (3)] TURN RAPID SHUTDOWN SWICH TO THE OFF POSITION TO SHUT DOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN ARRAY LABEL 7 [NEC 690.56 (B), 690.4 (D) AND 705.10] LABEL 6 AT DIRECT-CURRENT EXPOSED RACEWAYS, CABLE TRAYS, COVERS AND ENCLOSURES OF JUNCTION BOXES, AND OTHER WIRING METHODS; SPACED AT MAXIMUM 10FT SECTION OR WHERE SEPARATED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS, OR FLOORS. [NEC 690.31(G)(3&4)] LABEL 3 TURN RAPID SHUTDOWN SWITCH TO THE OFF POSITION TO SHUT DOWN CONDUCTORS OUTSIDE THE ARRAY. CONDUCTORS WITHIN THE ARRAY REMAIN ENERGIZED IN SUNLIGHT  LABEL 8 FOR PV SYSTEMS THAT ONLY SHUT DOWN CONDUCTORS LEAVING THE ARRAY: SIGN TO BE LOCATED ON OR NO MORE THAN 3 FT AWAY FROM SERVICE DISCONNECTING MEANS TO WHICH THE PV SYSTEMS ARE CONNECTED AND SHALL INDICATE THE LOCATION OF ALL IDENTIFIED RAPID SHUTDOWN SWITCHES IF NOT AT THE SAME LOCATION. [NEC 690.56 (C) (1) (B)] LABEL 4 EQUIPMENT CONTAINING OVERCURRENT DEVICES IN CIRCUITS SUPPLYING POWER TO A BUSBAR OR CONDUCTOR SUPPLIED FROM MULTIPLE SOURCES SHALL BE MARKED TO INDICATE THE PRESENCE OF ALL SOURCES [NEC 705.10] MAIN SERVICE PANEL LABELING DIAGRAM:1 LABEL 5 [NEC 690.54] 3 2 4 EXISTING SUB PANEL (IF WHERE POINT OF INTERCONNECTION IS MADE) 1 2 PV COMBINER SUBPANEL - AC DISCONNECT 1 5 IF USED TO COMBINE PV OUTPUT CIRCUITS 1 3 4 INVERTER (S) LABEL 9 A RAPID SHUTDOWN SWITCH SHALL HAVE A LABEL LOCATED ON OR NO MORE THAN 3 FT FROM THE SWITCH THAT INCLUDES THIS WORDING. THE LABEL SHALL BE REFLECTIVE, WITH ALL LETTERS CAPITALIZED AND HAVING A MINIMUM HEIGHT OF 3/8 IN., IN WHITE ON RED BACKGROUND. [NEC 690.56 (C)] AC JUNCTION BOX OR COMBINER BOXDC ELECTRIC SHOCK HAZARD WARNING TERMINALS ON BOTH LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION ! THIS EQUIPMENT IS FED BY MULTIPLE SOURCES. TOTAL RATING OF ALL OVERCURRENT DEVICES, EXCLUDING MAIN SUPPLY OVERCURRENT DEVICE, SHALL NOT EXCEED AMPACITY OF BUSBAR. ! WARNING! DUAL POWER SUPPLY WARNING SOURCES: UTILITY GRID AND PV SOLAR ELECTRIC SYSTEM ! 8 WARNING: PHOTOVOLTAIC POWER SOURCE SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN SOLAR ELECTRIC PV PANELS SOLAR ELECTRIC PV PANELS RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM 2 2 2 2 LABEL 10 EACH PV SYSTEM DISCONNECTING MEANS SHALL PLAINLY INDICATE WHETHER IN THE OPEN (OFF) OR CLOSED (ON) POSITION AND BE PERMANENTLY MARKED: “PV SYSTEM DISCONNECT” OR EQUIVALENT. [NEC 690.13(B), 690.15 AND 705.20] 10 WHERE ALL TERMINALS OF THE DISCONNECTINGS MEANS MAY BE ENERGIZED IN THE OPEN POSITION, A WARNING SIGN SHALL BE MOUNTED ON OR ADJACENT TO THE DISCONNECTING MEANS. ALL INTERACTIVE SYSTEM(S) POINTS OF INTERCONNECTION WITH OTHER SOURCES SHALL BE MARKED AT AN ACCESSIBLE LOCATION AT THE DISCONNECTING MEANS AS A POWER SOURCE AND WITH THE RATED AC OUTPUT CURRENT AND THE NOMINAL OPERATING AC VOLTAGE. PERMANENT WARNING LABELS SHALL BE APPLIED TO DISTRIBUTION EQUIPMENT. A PERMANENT WARNING LABEL SHALL BE APPLIED TO THE DISTRIBUTION EQUIPMENT ADJACENT TO THE BACK-FED BREAKER FROM THE INVERTER. [NEC 705.12 (B) (3) (2)] BUILDINGS WITH PV SYSTEMS SHALL HAVE A PERMANENT LABEL LOCATED AT EACH SERVICE EQUIPMENT LOCATION TO WHICH THE PV SYSTEMS ARE CONNECTED OR AT AN APPROVED READILY VISIBLE LOCATION AND SHALL INDICATE THE LOCATION OF RAPID SHUTDOWN INITIATION DEVICES. THE LABEL SHALL INCLUDE A SIMPLE DIAGRAM OF A BUILDING WITH A ROOF AND SHALL INCLUDE THE FOLLOWING WORDS: THE TITLE “SOLAR PV SYSTEM IS EQUIPPED WITH RAPID SHUTDOWN” SHALL UTILIZE CAPITALIZED CHARACTERS WITH A MINIMUM HEIGHT OF 3/8 IN. IN BLACK ON YELLOW BACKGROUND, AND THE REMAINING CHARACTERS SHALL BE CAPITALIZED WITH A MINIMUM HEIGHT OF 3/16 IN. IN BLACK ON WHITE BACKGROUND. (1) BUILDINGS WITH MORE THAN ONE RAPID SHUTDOWN TYPE. FOR BUILDINGS THAT HAVE PV SYSTEMS WITH BOTH RAPID SHUTDOWN TYPES OR A PV SYSTEM WITH A RAPID SHUTDOWN TYPE AND A PV SYSTEM WITH NO RAPID SHUTDOWN, A DETAILED PLAN VIEW DIAGRAM OF THE ROOF SHALL BE PROVIDED SHOWING EACH DIFFERENT PV SYSTEM AND A DOTTED LINE AROUND AREAS THAT REMAIN ENERGIZED AFTER THE RAPID SHUTDOWN SWITCH IS OPERATED. INVERTER OUTPUT CONNECTION DO NOT RELOCATE THIS OVER CURRENT DEVICE MAIN PHOTOVOLTAIC SERVICE DISCONNECT PHOTOVOLTAIC AC DISCONNECT WARNING 12.5 V AC M MSP LC JB SITE INFORMATION DEBORAH ANNE AYRS 4405 E AVE ANACORTES, WA 98221 DC System Size: 4.50 kW DC Lat, 48.48544 Long, -122.63078 (10) VSUN450 -144BMH-DG (450W) PV Modules Inverter(s) PUGET SOUND ENERGY DRAWN BY: B CUTANDA DATE: 05/15/2023 9981 West 190th St Unit K Mokena IL 60448 T: 708-995-1643 Revolution Energy Systems Inc. (2)HOYMILES HM-1200N (240V) (1) HOYMILES HM-600N (240V) AC System Size: 3.00 kW AC / 3.00 kVA CAUTION POWER TO THIS BUILDING IS ALSO SUPPLIED FROM ROOF MOUNTED SOLAR ARRAYS WITH SAFETY DISCONNECTS AS SHOWN: 4405 E AVE, ANACORTES, WA 98221 DIRECTORY PERMANENT PLAQUE OR DIRECTORY PROVIDING THE LOCATION OF THE SERVICE DISCONNECTING MEANS AND THE PHOTOVOLTAIC SYSTEM. (ALL PLAQUES AND SIGNAGE WILL BE INSTALLED AS OUTLINED WITHIN: NEC 690.56(B)&(C), [NEC 705.10]) PLACARD - PV08 PV ARRAY UTILITY METER AC DISCONNECT MAIN DISTRIBUTION UTILITY DISCONNECT LOAD CENTER SITE INFORMATION DEBORAH ANNE AYRS 4405 E AVE ANACORTES, WA 98221 DC System Size: 4.50 kW DC Lat, 48.48544 Long, -122.63078 (10) VSUN450 -144BMH-DG (450W) PV Modules Inverter(s) PUGET SOUND ENERGY DRAWN BY: B CUTANDA DATE: 05/15/2023 9981 West 190th St Unit K Mokena IL 60448 T: 708-995-1643 Revolution Energy Systems Inc. (2)HOYMILES HM-1200N (240V) (1) HOYMILES HM-600N (240V) AC System Size: 3.00 kW AC / 3.00 kVA SITE PHOTOS - PV09 SITE PHOTOS: