HomeMy WebLinkAboutPermit File BLD-2019-0511 1715 O Avenue (48)TLI)- 2oi9i4S�1 Evergreen Certified, LLC 502 Rainier Ave S, Suite 206 Seattle, WA 98144 www.evergreencertified.com MADRONA REAL ESTATE SERV1C,'ES, 11.( WHOLE BUILDING AIR -LEAKAGE TEST REPORT Scope of work: Whole building air -tightness test conducted at 1715 0 Ave, Anacortes, WA. Test date: 03/26/2022 Testing Summary: 1 Evergreen Certified, LLC. was contracted by Madrona Real Estatt Services, LLC. to perform Whole Building Air Leakage Testing in accordance with ASTM E779 per the requirements specified by the 2015 Washington State Energy Code, Commercial Provisions section C402.5: Air leakage -thermal envelope. The building was tested using pressurization and depressurizatibn with a final combined result of 0.306CFM/Ft2 of envelope at 75Pa with the c6de maximum allowable air leakage rate of the building envelope at 0.40 CFM/>~t2 of at 75Pa. The test was performed in accordance with the attached report. Summary of TestinLy Data: Test Conditions Air Flow CFM @ 75 Pa Air Change Rate ACH @ 75Pa ! Enclosure Tightness CFM ft2 @ 75Pa Depressurization 7,170.8 1.95 1 0.256 Pressurization 9,990.0 2.72 0.357 Average 8,580.5 2.34 0.306 C402.5 Requirements 11,209 N/A 0.40 Fan rnlihrntinn ri-rtifirntP RPtrnter S0f)(1- Retrotec 5000 SFN103025 Fan last calibrated: (Flow Equation Parameters - SFN103025131). Published Flow Equation Parameters, Round 81. CFM Range n K K1 K2 K1 K4 MF Open 0.498 548 0 0.3 0 ! 1 10 A 0.502 287 0 0.4 0 1 20 88 0.54 113.25 0 0.7 0 1 40 Polynomial Range g f a b c ! d K2 MF 84 29 -0.19 0.000007943 -0.00864 4.9 206 0.8 40 B2 30 0.1 0.00000088 -0.0029 2.15 90 1 50 81 30 0 0.0000005 -0.00128 1.02 54 1 60 B74 25 0.15 0.000000796 -0.00095 0.59 18 0.8 35 B47 25 0.09 0.000000269 -0.0003591 0.2435 12.05 1 50 B29 25 -0.02 0.000000111 -0.000149 0.0921 4.4 0.6 50 Fan Pressure FP is the measured fan pressure when using a self -referenced fan or when Room Pressure (RP) is ( ) negative. If using a fan which is not self -referenced, and Room Pressure is positive, Fart Pressure is calculated by subtracting the measured Room Pressure from the Absolute Value of the Fan Pressure. If PrA>0 and fan is not self -referencing: FP = PrB I-PrA If PrA<0 or fan is self -referencing: FP = PrB Flow calculations are not valid if Fan Pressure is less than either IVIF or (K2 x I RP 1). Flow in CFM using the above coefficients is calculated as follows for standard Ranges: flow = (FP — (IRPI x K1) )N + (K + (K3 x FP)) Flow in CFM using the above polynomial coefficients is calculated as follows: f low = (a x W) + (b x W) + (c x FP) + d + ((g — ARP I) x f ) Page 110 Test Equipment j The following test equipment was used in the performance of the air leakage tests. Fan Fan serial Fan location Gauge Gauge serial Gauge Calibration #1 Retrotec 5000 5FN102507 1st Floor North Door DM32 411966 08/07/2020 #2 Retrotec 5000 5FN103025 1st Floor North Door DM32 407606 12/14/2017 Fan Calibration Certificate Retrotec 5000: Retrotec 5000 SFN102507 Fan last calibrated: (Flow Equation Parameters - SFN10?50781). Flow Equation Parameters, Round 81. CFM Published Range n K K1 K2 1(3l K4 MF Open 0.498 548 0 0.3 0I, 1 10 A 0.502 287 0 0.4 01 1 20 B8 0.54 113.25 0 0.7 0 1 40 Polynomial Range g f a b c d K2 MF B4 29 -0.19 0,000007943 -0.00864 4.9 206 0.8 40 B2 30 0.1 0,00000088 -0.0029 2.15 90 1 50 B1 30 0 0.0000005 -0.00128 1.02 54 1 60 B74 25 0.15 0.000000796 -0.00095 0.59 18 0.8 35 B47 25 0.09 0.000000269 -0.0003591 0.243 12.05 1 50 B29 25 1-0.02 1 0,000000111 -0.000149 0.0921 4.4 0.6 50 Page 19 Baseline, initial [Pa] -0.89 -0.83 -0.64 -0.47 -0.49 -0.64 -0.63 -0.50 -0.52 -0.65 -0.62 1 -0.67 Baseline, final [Pa] -0.16 0.00 0.03 1 -0.15 1 -0.08 -0.13 -0.39 -0.33 -6148 -0.50 -0.76 1 -0.82 Flow vs Induced Pressure (Pressurize Set) 100000, 1000-'-T 10 Building Gauge Pressure (Pressurize Set) 100-1 F--*. kmL-.A 70 60 iv 50 D tn a 40 30 v t Pmmriu r - 0.9905 . ,� :� * �Llb (Log) Pressure (Pa) 100 f -10 -20- 0 200 400 600 800 Tame fl Page 18 Pressurize Data Set Test Dataset Date: 03/26/2022 Start time: 13:34:23 Environmental Conditions Wind speed: 3.13 from th W Operator Location: Inside the building Initial Bias Pressure: -0.63 Pa Final Bias Pressure: -0.31 Pa Average Bias Pressure: -0.47 Pa Initial Temperature: indoors: 67 °F 1 outdoors: 55 T Final Temperature: indoors: 67 T outdoors: 55 °F Test Analysis Results: Uncertainty: Height x Temperature difference: 684 ft OF Air leakage coefficient, C: 522 CFM/Pa" +/-13.15 Exponent, n: 0.683 +/- 4.6836 Correlation coefficient, r: 0.99835 Air flowsTP: 9990.0 CFM at 75 Pa +/-1.9 Air change rate: 2.723 air changes / hour at 75 Pa +/-1.9 Flow per unit floor area: 0.4222 CFM per sq ft +/-1.9 Flow per unit envelope area: 0.357 CFM per sq ft +/-1.9 Equivalent leakage area at 10 Pa [sq in] 741.9 +/-5.1 Effective leakage area at 4 Pa [sq in] 382.6 +/-8.3 LEED Permeability at 4 Pa [sq in/ 100 sq ft] 1.365 +/-8.3 Measured pressure [Pa] 75.0 68.3 62.2 57.7 51.9 46.0 40.7 34.8 29.3 24.1 Induced Pressure [Pa] 75.5 68.8 62.7 58.2 52.4 46.5 41.1, 35.3 29.8 24.6 #1, Range Open Fan Pressure [Pa] 161.6 143.9 128.5 117.7 103.1 89.3 77.8' 64.5 52.5 41.4 Flow [CFM] 4867 4530 4245 1 4042 1 3734 1 3434 1 3181 2840 1 2507 1 2177 #2, Range Open Fan Pressure [Pa] 154.0 139.2 128.2 113.9 101.4 87.2 80.3, 67.2 53.5 41.2 Flow [CFM] 5019 4763 4587 4238 3980 3631 3549 3207 2784 2340 Total Flow (CFM] 9885.05 9292.76 8832.73 8280.11 7714.55 7065.64 6736.15 6046.64 5290.67 4516.41 Corrected Flow [CFM] 9975.1 9377.3 8913.1 8355.5 7784.8 7130.0 679 A 6101.7 5338.8 4557.5 Error (%] -0.6% -0.5% 0.8% -0.6% -0.5% -1.1% 2.4% 2.2% 0.4% -2.3% 10 induced pressures each taken for 20 of the required 20 seconds. 12 baseline pressures each taken for 10 of required 10 seconds. Average Baseline, AP: -0.47 Pa Static Pressure Averages: Average [Pa] AP -0.47 initial [Pa] AP01-0.63 AP01- -0.63 AP01+ 0.00 final [Pa] AP02 -0.31 AP02- -0.38 AP02+ 0.03 Page 17 Initial [Pa] AP01-0.57 1 � iP01+ 0.00 Final [Pa] AP02 -0.42 1 OP02- -0.42 AP02+ 0.00 Baseline, initial [Pa] -0.37 -0.81 -0.36 -0.35 -0.38 -0.41 -0.62 -0.76 -0.71 -0.70 1 -0.65 -0.76 Baseline, final [Pa] -0.49 -0.44 -0.40 -0.31 -0.31 -0.42 -0.55 -0.59 -0',44 -0.45 -0.35 -0.29 Flow vs Induced Pressure (Depressurize Set) 10000 I000 �Wg) rressure (Ka) Building Gauge Pressure (Depressurize Set) Page 16 Air Leakage Test Data Appendix Depressurize Data Set Test Dataset Date: 03/26/2022 Start time: 13:53:21 Environmental Conditions Wind speed: 3.13 from the W Operator Location: Inside the building Initial Bias Pressure: -0.57 Pa Final Bias Pressure: -0.42 Pa Average Bias Pressure: -0.49 Pa Initial Temperature: Indoors: 67 °F Outdoors: 5� °F Final Temperature: Indoors: 67 °F Outdoors: 55 °F Test Analysis Results: Uncertainty: Height x Temperature difference: 684 ft °F Air leakage coefficient, C: 614 CFM/Pa" +/-1.07 Exponent, n: 0.569 +/- 0.4857 Correlation coefficient, r: 0.99998 Air flowsTP : 7170.8 CFM at 75 Pa +/-0.2 Air change rate, ACH: 1.955 air changes per hour at 750a +/-0.2 Flow per unit floor area: 0.3031 CFM per sq ft +/-0.2 Flow per unit envelope area: 0.256 CFM per sq ft +/-0.2 Equivalent leakage area at 10 Pa [sq in] 670.4 +/-0.4 Effective leakage area at 4 Pa [sq in] 1 383.8 +/-0.7 LEED Permeability at 4 Pa [sq in/ 100 sq ft] 1 1.370 +/-0.7 Measured pressure [Pa] -78.2 -68.8 -63.0 -57.9 -52.2 -46.4 -401 -35.4 -29.2 -23.9 Induced Pressure [Pa] -77.7 -68.3 -62.6 -57.4 -51.7 -45.9 -39;7 -34.9 -28.7 -23.4 #1, Range Open Fan Pressure [Pa] 49.6 42.9 38.7 35.4 31.3 27.3 22. 19.9 15.5 11.8 Flow [CFM] 3828 1 3564 1 3385 1 3237 3043 2843 2669 2428 2145 1 1874 #2, Range Open Fan Pressure [Pa] 44.8 38.1 34.3 31.0 27.6 24.2 20.7 17.8 14.6 12.0 Flow [CFM] 3642 3356 3188 3029 2862 2677 1 247 R 1 2301 2086 1891 Total Flow [CFM] 7469.76 6920.67 6573.3 6265.12 5904.26 5520.29 5087.40 4729.43 4230.54 3765.94 Corrected Flow [CFM] 7282.5 6747.2 6408.5 6108.1 5756.3 5381.9 4959.9 4610.9 4124.5 3671.5 Error [%] 0.3% 0.0% -0.2% -0.1% 0.0% -0.1% 0.0 0 0.1% 0.1% 0.0% 10 induced pressures each taken for 20 of the required 20 seconds. 12 baseline pressures each taken for 10 of required 10 seconds. Average Baseline, AP: -0.49 Pa I Static Pressure Averaees: I I I I I Average Baseline [Pa] I AP -0.49 1 1 1 1 Page (5 100000 U. u 9 1 U- 0 1000 10 Pressurizer a 0.99835 t * to Depressurize r*— * ' 4 (Log) Pressure (Pa) 100 Page 14 Combined Test Data (Average Values) Results uncertai 'ty Air flowsrP, [CFM at 75] 8580.5 +/-1.0% Air change rate at 75 Pa [/h] 2.34 +/-1.0% Flow per unit floor area at 75 [CFM/sq ft] 0.363 +/-1.0% Flow per unit envelope area at 75 [CFM/sq ft] 0.306 +/-1.0% Equivalent leakage area at 10 Pa [sq in] 706.1 +/-2.8% LBL Effective leakage area at 4 Pa [sq in] 383.0 +/-4.5% LEED Permeability at 4 Pa [sq in/ 100 sq ft] 1.370 +/-4.5% iv 4 a c Page 13 Summary: FanTestic Version: 5.12.54 Licensed to: evergreen Certified Test date: 03/26/2022 By: Cybil Tribie By: Greta Tjeltveit Customer Information: Madrona Real Estate Services, LLC. Building address: 1715 O Ave Anacortes, Skagit County WA, USA, 98221 Building and Test Information Test file name: ASTM2019 2022-03-261456 Building volume [cu ft]: 220,130 Envelope Area [sq ft]: 28,022 Floor Area [sq ft]: 23,660 Building Height (from ground to top) [ft]: 57 Results CFM at 75 Pa: 8580.5 Leakage Area (EgLA) [sq in]: 706.1 Leakage Area (EfLA) [sq in]: 383.0 Air Changes per hour ACH75: 2.34 Assumptions and warnings While FanTestic software may calculate air leakage results based on user input, use of1his software does not in any way guarantee these results. Building Information 5-Story Apartment Building Building Measurements Building Volume [cu ft]: 220,130 Envelope Area (AE) [sq ft]: 28,022 (Defined as the area of external walls plus the area of the roof and ground floor.) Net Floor Area (Af) [sq ft]: 23,660 Building Height (from ground to top) [ft]: 57 Test Method All intentional openings were set to the operating condition expected during occupancy. Discussion of Results Leakage rate The measured air flow at a test pressure of 75 Pa was 8580.5 CFM which equates to a In equivalent leakage area of 706.1 sq in, based on adding up the leakage from all the holes and cracks in the exterior. This leakage also equates to a one inch gap, 58.84 feet long. Your home leaks as if there is one hole this size in the wall. Page 12 Air Leakage Test Report In compliance. wiih ASTM E-779-10 (2019) ,FVERG REEN CERTIFIED 5- Story Apartment Building Building Address: 1715 O Ave Anacortes, Skagit County WA, USA, 98221 Performed for: Madrona Real Estate Services, LLC. Performed by: Cybil Tribie Greta Tjeltveit Test date: 03/26/2022 Page I 1