Blower Door Air Leakage Test Results
Jobsite Address: 1505 Harbor View Ct PNWES Rep: Hugo Prado
City,State Anacartes Contractor:PNW Energy Servrces
Zip 98221 License#:PNWENE579977
f �
Date Calculated Air Changes Per Hour
8f31f2021 3, 14
wi L_
R402.4.1.2 Testing.The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding 5 air changes per hour.Testing
shall be conducted with a blower door at a pressure of 0.2 Inches wig.(50 Pascals).Where required by the code official,testing shall be conducted by an
approved third party.A written report of the results of the test shall be signed by the party conducting the test and provided to the code official_Testing
shall be performed at any time after creation of all penetrations of the building thermal envelope.Once visual inspection has confi d sealing t he test.
Table R402.4.1.1),operable windows and doors manufactured by small business shall be permitted to be sealed off at the frame prior
While Performing Blower Door Test:
Exterior windows and doors,fireplace and stove doors shall be closed,but not sealed,beyond the intended weatherstripping or other infiltration control
measures.
Dampers including exhaust,intake,makeup air,backdraft and flue dampers shall be dosed,but not sealed beyond intended infiltration tontrn
measures.
Interior doors,if installed at the time of the test,shall be open.
Access matches to conditioned crawl spaces and conditioned attics shall be open.
Exterior openings for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
Heating and cooling systems,if installed at the time of the test,shall he turned off.
Supply and return registers,if installed at the time of the test,shall be fully open.