Loading...
HomeMy WebLinkAboutDOC-2009-Plan Review DOH - Letter of Transmittal Washington State Department of November 19, 2009 i* Health Construction Review Services 310 Israel Rd.SE Tumwater,WA 98501 --- -- ___----------- —_—� PO Box 47852 Olympia,Washington 98504-7852 www.doh.wa.gov/crs tel.360-236-2944 fax.360-236-2901 Ii Project Info: CRS#60112372 Project 1300 "O" Ave Chandlers Square location: Anacortes,WA 98221 Chapter 388-78A WAC Boarding Homes Independent Living Wing Local Permit#: BL-2009-0293 Key People: Assigned DOH Richard M. Swanson,RA Reviewer: richard.swanson@doh.wa.gov Facility Anacortes Senior Housing LLC Facility Contact: Anacortes Senior Housing LLC Administrator: Paul Dendy Peter Kovach 1300"O" Ave 1300"O" Ave Anacortes,WA 98221 Anacortes,WA 98221 (360)882-4500 (360)293-1300 paut@milestoneretirement.com director@chandlersquare.com Architect/ Mark Christ Architect Building City of Anacortes Engineer: Mark Christ Official: Don Measamer 810 Bennett St PO Box 547 Sedro-Woolley,WA 98284 Anacortes WA 98221 (360)855-1546 (360)293-1901 mark@markchrist.com don@cityofanacortes.org Sprinkler / N/A Fire Alarm N/A Contractor: Contractor: Other: N/A Other: N/A Copies To:® Local Building Official:City of Anacortes ❑ DOH Child Birth Center Licensing ® Architect/Engineer:Mark Christ Architect ❑ DOH Office of Accommodations&Res.Care Survey ❑ Sub-Contractor:N/A ❑ DOH Office of Investigations&Inspections ❑ Sub-Contractor:N/A ❑ DSHS, ,Div.Of Alcohol and Substance Abuse ❑ Other: ® DSHS,Amy Robertson,Aging&Adult Services Administration ❑ Washington State Patrol,Fire Protection Bureau ® L&I,Bill Eckroth,Electrical Section ® CRS File ❑ L&I,John Harvey,Factory Assembled Structures Page 1 of 8 Plan Review Comments for Project#60112372 Items required prior to licensing: ®Notification of Construction Complete Card Chandlers Square ❑Reduced Floor Plan Chapter 388-78A WAC Boardin Homes ❑Certificate of Occupancy/Local AHJ Approval g ❑Updated Functional Program Independent Living Wing Memo: Review only covers that portion of the construction documents that involves remodeling of an existing boarding home unit for use as Storage 220 & Corridor 221, and the addition of Connection 219 & Dining 222. - NOT APPROVED - - REVISE AND RESUBMIT - This project is not approved and is not yet authorized for use by the Licensing Agency. Provide written responses to our review for those items checked as not approved. To help expedite our review include a transmittal with all submissions clearly identifying all documents with your project name and CRS project number. Include two copies of revised plans or sheets, in the same format/size as the original submission, incorporating your corrections. Any response that does not address ALL the review comments and provide the required information will be considered incomplete and may be returned without review. All documents submitted will be retained in our office until all the construction documents have been received, reviewed, and accepted. When the project is approved, a complete package of documents will be stamped and signed by the department. One copy will be returned to the facility administrator and one retained for our records. If you have any questions please feel free to contact Construction Review Services. You can monitor project status and fill out our online survey at www.doh.wa.gov/crs. Page 2 of 8 Plan Review Comments for Project#60112372 Facility Data Certificate: Facility Name: Chandlers Square Licensee UBI#: 601727818 Site Address•• 1300 "O" Ave Critical Access Facility: ❑ Yes ® No Anacortes,WA 98221 Estimated Date of Occupancy: 03/10 Occupancy R2 Construction 5-A Applicable Code: Group: Type: 2006 IBC Number of Current: 66 Added: 0 Removed: 1 Total: 65 a >4 Beds: >4 Automatic Fire Sprinkler System: ® Yes ❑ No Type 13R aAutomatic Fire Alarm System: ® Yes ❑ No dCompartmentation req'd: ®Yes ❑No Smoke Control System Provided: ❑ Yes ®No w aSpecial Delayed Egress Control: ❑Yes ®No Location: Certificate of Need Required: ❑ Yes ❑No CON Approval Granted: ❑ Yes ❑No CON Number : Number of units: Private occupancy: Two person occupancy: Based on size of rooms used for sleeping Residents az O Based on size of common rooms Residents cn F, Maximum allowable licensable beds: A *4 Qualifies for Assisted Living Funding Program ❑ Yes ❑No Number of qualifying units: U W F� °z The data above is based on the information presented to CRS. Any change in the facility or facility program that causes the above information to be incorrect is subject to review by CRS.Approval for construction is not approval for licensure.A copy of the facility data certificate will be sent to the licensing agency. Page 3 of 8 Plan Review Comments for Project#60112372 Chandlers Square Chapter 388-78A WAC Boarding Homes Independent Living Wing � b o a The following are plan review comments: o a o U Q Z 1 ❑x Construction and renovation may create conditions that compromise the health and safety of residents, staff, and visitors. Facility planning must include, in addition to space and operational needs, provisions for infection control and safety of the facility's occupants during any renovation or new construction. WAC 388-78A-2850(3) Per the Infection Control Procedure information the proposed construction is i to be separated from existing portions of the facility by existing wall assemblies and/or 6 mil plastic sheet barriers. The Contractor will be directed to keep the existing corridor clear of tools, supplies, and debris materials. IArchitect response received 10106109—Shall comply, a copy of the ICP ha s been provided to Chandler's Square Facility Contact and general Contractor and is incorporated into the Construction documents. 2 [H] Provide electrical drawings pertaining to the boarding home portion of the facility and its exiting stamped and signed by a Washington state licensed architect or engineer. WAC 388-78A-2820(1)(b)(i)(A) Architect response received 10106109—Shall comply, enclosed please find(2) sets of Electrical Drawings stamped and signed by the Architect. Approved 11/13/09—Electrical drawings El —E10 have been stamped and signed by the architect. 3 0 Per the functional program the independent residents shall be allowed to dining and activities with the boarding home residents. Provide drawings showing how the combined facility will provide at least twenty square of common area for the combined total number of the residents, both boarding home and independent, as if all were boarding home residents. WAC 388-78A-3050(2)(b) Architect response received 10106109—Attached please find CRS letter dated March 12th, 2009 which documents the existing facility is occupied by 78 residents requiring 1,560 square feet of common space. Per the March 12th floor plans, the existing facility contains 3,000 square feet of common space Page 4 of 8 Plan Review Comments for Project#60112372 excluding Private Dining Room#264. There has been no change to the existing facility since March 12`h, 2009. The 25 apartment Independent Living Wing is potentially occupied by a maximum of 50 residents. The Independent Living Wing contains 350 square foot Lobby#216 and a 653 square foot Rec. Room#124 (1,003 square feet)of common space for use by Independent Living Residents. The new construction will also include a 396 square foot Dining Room Addition and an 843 square foot Connection/Assembly (1,239 square feet) to be used in common by both the existing facility and the independent living wing residents. The total of occupants is 78 (existing)— 1 (apartment removed) + 50 (new independent) = 127 residents requiring 2,540 square feet of common space. The facility contains over 3,000 + 1,239 = 4,239 square feet of common space to be used by all residents. There is also 1,003 square feet of common space to be used by the independent living wing residents. Approved 11/13/09—Per the written response a maximum of 50 occupants will be added to the complex. Between the Dining Room Addition and the Connection/Assembly area more than the minimum 20 square feet per resident for common area will be added. 4 ❑x Provide a drawing locating a means of communication in Connection 219 for residents and staff to contact on-duty staff in an emergency. WAC 388-78A-2930(1)(a)(ii) Architect response received 10106109—Shall comply, Shop Drawings of emergency call system shall be provided by Commercial Alarm &Detection. It is intended to be a wireless system consisting of pendants for residents, radios for staff, and wall mounted wireless devices installed at required locations. Shop Drawings are to be reviewed and approved by CRS prior to installation. See Deferred Submittals on sheet Al. Noted 11/13/09—The means of communication documents shall be submitted as a deferred submittal. 5 0 Provide manufacturer's labeled carpet specifications and radiant panel test report for each carpet style used in and exiting from the boarding home licensed portions of this project. WAC 388-78A-2850(1)(b)(vi), and Section 804, International Building Code Architect response received 10106109—Shall comply, attached please find Addendum#1. Project Manual Items#6, #7, and#8 specify the carpet and pad to be uses. Attached please also find radiant panel test reports. Not Approved 11/13/09—Carpet styles Sable Island and Legend Falls by Page 5 of 8 Plan Review Comments for Project#60112372 Philadelphia Commercial are approved for direct glue-down installation. However,per Project Manual Items#7 and#8 carpeting is to be installed over pads and not direct glued as was how the carpets were tested. Provide revised information removing the pads and directly securing the carpet to the floor,or provide information showing the carpet with pad testing reports and how the carpet/pad assembly qualifies as carpet with nonskid backing. 6 ❑x Provide a drawing showing the potential layout of table and chairs in Dining Addition 222 for verification an aisle exit access to exit Door 186 can be maintained. WAC 388-78A-2910(1), Sec. 1014.4 International Building Code Architect response received 10106109—Shall comply, attached please find supplemental drawing SDI dated 09128109. The table%hair spaces indicated include the table width plus 19" each side for chairs (IBC 1014.4.3). The distance between the table%hair spaces is required to be a minimum of 0.15"x 4 chairs =0.6" (IBC 1014.4.3.2 exception and TBL 1005). Per IBC 1109.11, a minimum of 5% of the total Dining Room seating (2 spaces)are accessible per ICC ANSI A117.1. Approved 11/13/09—Per SD1 dated 09/28/09 the tables and chairs can be arranged to provide seating for 26 while maintaining at least a 44"aisle to exit Door 186. 7 0 Provide revised drawings showing/verify the existing exterior of the boarding home on each side of the 2-hr. fire wall and roof overhang are a one-hour rated assemblies with 3/4 hr. rated openings, or explain why the building code does not require the ratings of the adjoining surfaces. WAC 388-78A-2910(1), Sec. 705.5.1 International Building Code Architect response received 10106109—Shall comply, Please see detail F/A16. The 2 hour fire wall is required to be designed in accordance with IBC Section 705. 1) Per IBC 705.5 Horizontal continuity, Exception 3.: Fire walls shall be permit to terminate at the interior surface of noncombustible exterior sheathing where the building on each side of the fire wall is protected by an automatic sprinkler system installed in accordance with Section 903.3.L I or 903.3.1.2. According to the construction drawings the existing facility is constructed using 5/8" type X gypsum sheathing. This can be verified at the time of demolition. The exterior walls of Connection 219 shall be revised to be constructed using 5/8" type X gypsum sheathing in lieu of the OSB sheathing specified. All exterior wall shall have noncombustible exterior cement board siding. Not Approved 11/13/09—Per the written response the 2-hour fire wall may terminate at the interior surface of noncombustible exterior sheathing. This response does not address the comment requiring the intersected walls to be fire rated which is a separate issue. Page 6 of 8 Plan Review Comments for Project#60112372 8 ❑x Provide revised drawings showing/verify the existing exterior of the boarding home vertically above the proposed 2-hr. fire wall is a one-hour rated assembly with 3/4 hr. rated openings, or explain why the building code does not require the ratings of the above new roof surfaces. WAC 388-78A-2910(1), Sec. 705.6.1 International Building Code Architect response received 10106109—Shall comply, Please see detail F/A16. The 2 hour fire wall is required to be designed in accordance with IBC Section 705. Per IBC 705.6.1 Stepped Buildings, Exception: Where the fire wall terminates at the underside of the roof sheathing, deck or slab of the lower roof provided: 2) The lower roof assembly within 10 feet of the wall has not less than a 1- hour fire-resistance-rating and the entire length and span of supporting elements for the rated roof assembly has afire-resistance rating of not less than I hour. 3) Openings in the lower roof shall not be located within 10 feet of the fire wall. The I hour ceiling construction shall be installed per GA file no. RC 2601 The 2 hour wall construction shall be installed per UL Design No. U301 See enclosure to City of Anacortes Building Department review response letter, enclosed. Approved 11/13/09—Per the written response the roof construction will be a one- hour fire resistance rated assembly. It is assumed no openings will be located within 10 feet of the fire wall. It is also assumed the City of Anacortes approves this design even though a copy of the review response letter was not located. 9 ❑x Provide revised Sheet Al showing the two new patios accessed from Doors 05 &06 and the new sidewalk accessed from Door 186 connected to the public way with direct and unobstructed access. WAC 388-78A-2910(1), Sec. 1024.6 International Building Code Architect response received 10106109—Shall comply, attached please find revised drawing AI dated 09128109. In addition we will be submitting a Landscape Plan as a Deferred Submittal which will clearly identify the sidewalks and patios. Approved 11/13/09—Revised Sheet Al shows the two new patios connecting to the public way with direct and unobstructed access walkways. 10 x❑ Constructing Corridor 221 will create a dead end in excess of twenty feet. Provide revised drawings, or explain why this portion of the corridor system should not be considered a dead end. WAC 388-78A-2910(1), Sec. 1017.3 International Building Code Architect response received 10106109—Shall comply, attached please find supplemental drawing SD2 and AD2A dated 09128109. The maximum corridor Page 7 of 8 Plan Review Comments for Project#60112372 depth is 24'. Per IBC 1017.3 Dead Ends, Exception 3, the minimum with is 24'/2.5 = 9'-7 3/16" in order to avoid being a dead end corridor. The existing wall above door#58 has been removed to create a minimum with of 9'-11". Approved 11/13/09—Per drawing SD2A the minimum width will be 9'-11"allowing a deadend distance up to 24'-91h" which is greater than the 24'-7"or so that will occur when the new 2-hour wall is installed. 11 x❑ Provide two complete plans and specifications for the fire alarm system installation or modification for review and approval prior to system installation. Plans and specifications shall include, but not be limited to, a floor plan; location of all alarm- initiating and alarm-signaling devices; alarm-control and trouble-signaling equipment; annunciation; power connection; battery calculations; conductor type and sizes; voltage drop calculations; name, address, and phone number of the agency receiving off- premises transmission of alarm; and the manufacturer, model numbers, and listing information for all equipment, devices, and materials. Incomplete Plans and specifications will be returned without review. Plans and specifications may be submitted separately from construction documents during the construction of the project. The department reserves the right to defer plan review and inspections to the local authority having jurisdiction (AHJ). Section 907.1, International Fire Code Architect response received 10106109—Shall comply, Fire Alarm System documentation shall be provided as a Deferred Submittal for CRS review and approval prior to installation. Noted 11/13/09—Fire alarm documents to be a deferred submittal. 12 0 Provide two sets of sprinkler system working plans for review and approval before any equipment is installed or remodeled. Deviation from approved plans will require permission. Plans and specifications including ydraulic calculations that are incomplete or are not stamped by a Washington State Licensed Fire Sprinkler Contractor, will be returned without review. Plans and specifications may be submitted separately from construction documents during the construction of the project. The department reserves the right to defer plan review and inspections to the local authority having jurisdiction (AHJ). Section 903.1, International Fire Code Architect response received 10106109—Shall comply, Sprinkler System documentation shall be provided as a Deferred Submittal for CRS review and approval prior to installation. Noted 11/13/09—Fire sprinkler documents to be a deferred submittal. Compliance with the comments above provided by the Department of Health, Construction Review Services,are necessary for this facility to meet the requirements of the applicable licensing regulations found in the Washington State Administrative Code and associated references. These comments do not relieve the facility from the responsibility to meet the requirements of any other applicable federal, state or local regulations. In the event of conflicts between other jurisdictions and these written comments, the most stringent shall apply. Page 8 of 8 Plan Review Comments for Project#60112372