I am forwarding you a copy of the ICC interpretation I requested to document for my files.
Thank you for keeping me informed and getting an approved sheet All 8 to Casey at the job site.
Sincerely,
Mark Christ
-----Original Message-----
From: Doug Connell
To: Lis Valdemarsen
Cc: mark(a-)markchrist.com
Sent: Monday, December 28, 2009 10:26 AM
Subject: RE: 06 IRC M2301.2.2 (DC)
Code Edition: 2006 IBC
Code Section: 704.5
Questions: I have an R-2 occupancy that is VA construction. Per Table 601 and 602 the exterior
walls are required to be 1 hour fire rated construction. The exterior walls have a fire separation
distance greater than 5 feet. Do the fire-resistance rating for the walls have to be from both
sides—the interior side and the exterior side?
Answers: No, the exterior walls with fire separation distances of 5 feet or greater need only be
rated from the interior side of the wall.
This opinion is based on the information which you have provided. We have made no independent effort j
to verify the accuracy of this information nor have we conducted a review beyond the scope of your i
question. As this opinion is only advisory, the final decision is the responsibility of the designated
authority charged with the administration and enforcement of this code. j
James D. Connell, P.E.
Team Leader,A & E Services
International Code Council, Inc.
Birmingham District Office
900 Montclair Road
Birmingham, AL 35213
888-ICC-SAFE (422-7233), X5226 phone
dconnell(@-iccsafe.org
www.iccsafe.org
From: Lis Valdemarsen
Sent: Monday, December 21, 2009 5:11 PM
To: Doug Connell
Cc: 'mark@markchrist.com'
1/11/2010
Subject: 06 IRC M2301.2.2 (DC) Page 2 of 3
Mark,
I have forwarded your request to Doug Connell.
As the Holidays times are upon us there is staff that may be out and days when the offices are closed.
The days the offices are closed are as follows: Dec 24th 25th 31It and Jan 1st
Hope your holidays are wonderful for you and your family's.
If you have any questions regarding the status of your reply to your code opinion question, please contact me by
either phone or email.
Sincerely,
Lis Valdemarsen
Senior Secretary
International Code Council, Inc.
Los Angeles District Office
5360 Workman Mill Rd
Whittier, CA 90601-2298
Phone: (562) 699-0541 ext 3201
Fax: (562) 699-4522
IvaldemarsenQ-iccsafe.orq j
www.iccsafe.org
The Plan Review Services of ICC is ready and available to serve you for all of your plan review needs. Please contact us at
888/ICCSAFE or visit the ICC website for further information or assistance.
Did you know that all ICC National Certification Exams referencing the I-Codes®will be based on the 2009!-
Codes beginning January 1st 2010? Are you ready? Check out ICC Training to learn about the options ICC has
to help you get up to speed.
Feed: Codes, Standards &Guidelines: Request Code Opinion
Posted on: Monday, December 21, 2009 11:08 AM
Author: Mark Christ
Subject: mark christ
Requestor Full Name: mark christ
Job Title: architect
Phone Number: 360-855-1546
Fax: 360-855-1546
Requestor email address: mark@markchrist.com
Requestor Address: Mark Christ, Architect 810 bennett street sedro-woolley, WA 98284 USA
Code Reference: 2006 IBC Handbook Section 704.5. "For fire separation distances greater than 5 feet
the hazard is consudered to be predominantly form the inside of the building. See figure 704-9. Thus,
fire resistance rated construction whose tests are limited to interior fire exposure is considered
sufficient evidence of adequate fire resistance under these circumstances." "It should be noted that
this allowance is applicable regardless of why the wall requires a fire rating."
Code Edition: 2006 IBC
1/11/2010
Page 3 of 3
Code Section: 704.5
Questions: I have an R-2 occupancy that is VA construction. Per Table 601 and 602 the exterior walls
are required to be 1 hour fire rated construction. The exterior walls have a fire separation distance
greater than 5 feet. It is my understanding that per Section 704.5; the 1 hour fire rated exterior walls
are required to to be rated from the interior (fire side) only. could you please let me know if you agree
with my interpretation or expain otherwise?Thank you, Mark Christ
Status: New
View article...
i
I
1/11/2010
Mark and Lanney,
One item that was not addressed in my comments is that we need a landscape plan for review
and approval..
Thanks,
Don Measamer
City of Anacortes
Assistant Director, Planning &
Community Development,
Building Official