HomeMy WebLinkAboutCOR-2009-Plan Review DOH - Letter of Transmittal
September 23, 2009 Washington State Department of
fjHealth
Construction Review Services
310 Israel Rd.SE
Tumwater,WA 98501
. ....._ _ , PO Box 47852
Olympia,Washington 98504-7852
www.doh.wa.gov/crs
tel.360-236-2944
fax.360-236-2901
Project Info:
CRS# 60112372 Project 1300 "O" Ave
Chandlers Square location: Anacortes, WA 98221
Chapter 388-78A WAC Boarding Homes
Independent Living Wing Local Permit#:
Key People:
Assigned DOH Richard M. Swanson,RA
Reviewer: richard.swanson@doh.wa.gov
Facility Anacortes Senior Housing LLC Facility Contact: Anacortes Senior Housing LLC
Administrator: Paul Dendy Peter Kovach
1300"O"Ave 1300"O"Ave
Anacortes,WA 98221 Anacortes,WA 98221
(360)882-4500 (360)293-1300
paul@milestoneretirement.com director@chandlersquare.com
Architect/ Mark Christ Architect Building City of Anacortes
Engineer: Mark Christ Official: Don Measamer
810 Bennett St PO Box 547
Sedro-Woolley,WA 98284 Anacortes WA 98221
(360)855-1546 (360)293-1901
mark@markchrist.com don@cityofanacortes.org
Sprinkler / N/A Fire Alarm N/A
Contractor: Contractor:
Other: N/A Other: N/A
Copies To:
® Local Building Official:City of Anacortes ❑ DOH Child Birth Center Licensing
® Architect/Engineer:Mark Christ Architect ❑ DOH Office of Accommodations&Res.Care Survey
❑ Sub-Contractor:N/A ❑ DOH Office of Investigations&Inspections
❑ Sub-Contractor:N/A ❑ DSHS, ,Div.Of Alcohol and Substance Abuse
❑ Other: ® DSHS,Amy Robertson,Aging&Adult Services Administration
❑ Washington State Patrol,Fire Protection Bureau ® L&I,Bill Eckroth,Electrical Section
® CRS File ❑ L&I,John Harvey,Factory Assembled Structures
Page 1 of 6 Plan Review Comments for Project#60112372
Items required prior to licensing:
®Notification of Construction Complete Card
Chandlers Square ❑Reduced Floor Plan
�l ❑Certificate of Occupancy/Local AHJ Approval
Chapter 388-78A WAC Boarding Homes ❑Updated Functional Program
Independent Living Wing
Memo:
Review only covers that portion of the construction documents that involves remodeling of an existing
boarding home unit for use as Storage 220 & Corridor 221, and the addition of Connection 219 &
Dining 222.
- NOT APPROVED -
- REVISE AND RESUBMIT -
This project is not approved and is not yet authorized for use by the Licensing Agency.
Provide written responses to our review for those items checked as not approved. To help expedite our
review include a transmittal with all submissions clearly identifying all documents with your project name
and CRS project number.
Include two copies of revised plans or sheets, in the same format/size as the original submission,
incorporating your corrections. Any response that does not address ALL the review comments and provide
the required information will be considered incomplete and may be returned without review.
All documents submitted will be retained in our office until all the construction documents have been
received, reviewed, and accepted. When the project is approved, a complete package of documents will be
stamped and signed by the department. One copy will be returned to the facility administrator and one
retained for our records.
If you have any questions please feel free to contact Construction Review Services. You can monitor project
status and fill out our online survey at-,vNN,,-vN,,.doh.wa.gov/crs.
Page 2 of 6 Plan Review Comments for Project# 60112372
i
I
Facility Data Certificate:
Facility Name: Chandlers Square Licensee UBI#: 601727818
Site Address: 1300 "O" Ave Critical Access Facility: ❑ Yes ®No
Anacortes,WA 98221
Estimated Date of Occupancy: 03110
Occupancy R2 Construction 5-A Applicable Code:
Group: Type: 2006 IBC
W Number of Current: 66 Added: 0 Removed: 1 Total: 65
Beds:
Automatic Fire Sprinkler System: ® Yes ❑No Type 13R
aAutomatic Fire Alarm System: ® Yes ❑No
Compartmentation req'd: ®Yes ❑No Smoke Control System Provided: ❑ Yes ®No
w
aSpecial Delayed Egress Control: ❑ Yes ®No Location:
d
Certificate of Need Required: ❑ Yes ❑No CON Approval Granted: ❑ Yes ❑No
CON Number:
Number of units: Private occupancy: Two person occupancy:
Based on size of rooms used for sleeping Residents
az
O Based on size of common rooms Residents
F, F Maximum allowable licensable beds:
Aa Qualifies for Assisted Living Funding Program ❑ Yes []No Number of qualifying units:
W� U
GG �"
W
E�
O
z
The data above is based on the information presented to CRS. Any change in the facility or facility program that
causes the above information to be incorrect is subject to review by CRS.Approval for construction is not
approval for licensure.A copy of the facility data certificate will be sent to the licensing agency.
Page 3 of 6 Plan Review Comments for Project# 60112372
Chandlers Square
Chapter 388-78A WAC Boarding Homes
Independent Living Wing
Q
0
The following are plan review comments:
E Q
o �. o
U ¢ z
1 ❑x Construction and renovation may create conditions that compromise the health and safety
of residents, staff, and visitors. Facility planning must include, in addition to space and
operational needs,provisions for infection control and safety of the facility's occupants
during any renovation or new construction. WAC 388-78A-2850(3)
Per the Infection Control Procedure information the proposed construction is
to be separated from existing portions of the facility by existing wall assemblies
and/or 6 mil plastic sheet barriers. The Contractor will be directed to keep the
existing corridor clear of tools, supplies, and debris materials.
2 M Provide electrical drawings pertaining to the boarding home portion of the facility and its
exiting stamped and signed by a Washington state licensed architect or engineer.
WAC 388-78A-2820(1)(b)(i)(A)
3 ❑x Per the functional program the independent residents shall be allowed to dining and
activities with the boarding home residents. Provide drawings showing how the
combined facility will provide at least twenty square of common area for the combined
total number of the residents,both boarding home and independent, as if all were
boarding home residents. WAC 388-78A-3050(2)(b)
f
4 ❑x Provide a drawing locating a means of communication in Connection 219 for residents
and staff to contact on-duty staff in an emergency. WAC 388-78A-2930(1)(a)(ii)
5 ❑x Provide manufacturer's labeled carpet specifications and radiant panel test report for
each carpet style used in and exiting from the boarding home licensed portions of this
project.
WAC 388-78A-2850(1)(b)(vi), and Section 804, International Building Code
6 ❑x Provide a drawing showing the potential layout of table and chairs in Dining Addition
222 for verification an aisle exit access to exit Door 186 can be maintained.
WAC 388-78A-2910(1), Sec. 1014.4 International Building Code
Page 4 of 6 Plan Review Comments for Project# 60112372
7 El Provide revised drawings showing/verify the existing exterior of the boarding home on
each side of the 2-hr. fire wall and roof overhang are a one-hour rated assemblies with 3/4
hr. rated openings, or explain why the building code does not require the ratings of the
adjoining surfaces. WAC 388-78A-2910(1), Sec. 705.5.1 International Building Code
8 ❑x Provide revised drawings showing/verify the existing exterior of the boarding home
vertically above the proposed 2-hr. fire wall is a one-hour rated assembly with 3/4 hr. rated
openings, or explain why the building code does not require the ratings of the above new
roof surfaces. WAC 388-78A-2910(1), Sec. 705.6.1 International Building Code
9 ❑x Provide revised Sheet Al showing the two new patios accessed from Doors 05 & 06 and
the new sidewalk accessed from Door 186 connected to the public way with direct and
unobstructed access. WAC 388-78A-2910(1), Sec. 1024.6 International Building Code
i
10 ❑x Constructing Corridor 221 will create a dead end in excess of twenty feet. Provide
revised drawings, or explain why this portion of the corridor system should not be
considered a dead end.
WAC 388-78A-2910(1), Sec. 1017.3 International Building Code
11 ❑x Provide two complete plans and specifications for the fire alarm system installation or
modification for review and approval prior to system installation. Plans and
specifications shall include, but not be limited to, a floor plan; location of all alarm-
initiating and alarm-signaling devices; alarm-control and trouble-signaling equipment;
annunciation; power connection; battery calculations; conductor type and sizes; voltage
drop calculations; name, address, and phone number of the agency receiving off-
premises transmission of alarm; and the manufacturer, model numbers, and listing
information for all equipment, devices, and materials. Incomplete plans and
specifications will be returned without review. Plans and specifications may be
submitted separately from construction documents during the construction of the project.
The department reserves the right to defer plan review and inspections to the local j
authority having jurisdiction(AHJ). Section 907.1, International Fire Code
12 x❑ Provide two sets of sprinkler system working plans for review and approval before any
equipment is installed or remodeled. Deviation from approved plans will require
permission. Plans and specifications, including hydraulic calculations,that are
incomplete or are not stamped by a Washington State Licensed Fire Sprinkler Contractor,
will be returned without review. Plans and specifications may be submitted separately
from construction documents during the construction of the project. The department
reserves the right to defer plan review and inspections to the local authority having
jurisdiction (AHJ). Section 903.1, International Fire Code
Compliance with the comments above provided by the Department of Health, Construction Review Services, are necessary for this facility to meet
the requirements of the applicable licensing regulations found in the Washington State Administrative Code and associated references. These
comments do not relieve the facility from the responsibility to meet the requirements of any other applicable federal,state or local regulations.
In the event of conflicts between other jurisdictions and these written comments, the most stringent shall apply.
Page 5 of 6 Plan Review Comments for Project# 60112372